Data sheet6ES7155-6AA01-0BN0
SIMATIC ET 200SP, PROFINET bundle IM, IM 155-6PN ST, max. 32I/O modules and 16 ET 200AL modules, single hot swap, bundleconsists of: Interface module (6ES7155-6AU01-0BN0), Server
module (6ES7193-6PA00-0AA0), BusAdapter BA 2xRJ45 (6ES7193-6AR00-0AA0)
General informationProduct type designationHW functional statusFirmware versionProduct function● I&M data● Module swapping during operation (hotswapping)● Isochronous modeEngineering with● STEP 7 TIA Portal configurable/integrated as ofversion● STEP 7 configurable/integrated as of version● PROFINET as of GSD version/GSD revisionV14V5.5 SP4 and higherV2.3 / -Yes; I&M0 to I&M3Yes; Single hot swappingNoIM 155-6 PN STFS01V4.1Configuration controlvia datasetYesSupply voltageRated value (DC)24 V6ES7155-6AA01-0BN0Page 1/4
05/21/2020
Subject to change without notice
© Copyright Siemens
permissible range, lower limit (DC)permissible range, upper limit (DC)Reverse polarity protectionShort-circuit protectionMains buffering● Mains/voltage failure stored energy time19.2 V28.8 VYesYes10 msInput currentCurrent consumption (rated value)Current consumption, max.Inrush current, max.I²t450 mA550 mA3.7 A0.09 A²·sPowerInfeed power to the backplane bus4.5 WPower lossPower loss, typ.1.9 WAddress areaAddress space per module● Address space per module, max.Address space per station● Address space per station, max.512 byte; Dependent on configuration256 byte; per input / outputHardware configurationRack● Modules per rack, max.Submodules● Number of submodules per station, max.25632; + 16 ET 200AL modulesInterfacesNumber of PROFINET interfaces1; 2 ports (switch)1. InterfaceInterface types● Number of ports● integrated switch● RJ 45 (Ethernet)● BusAdapter (PROFINET)Protocols● PROFINET IO Device● Open IE communication● Media redundancyYesYesYes; PROFINET MRP2YesYes; Pre-assembled BusAdapter BA 2x RJ45Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FCInterface typesRJ 45 (Ethernet)6ES7155-6AA01-0BN0Page 2/4
05/21/2020
Subject to change without notice
© Copyright Siemens
● Transmission procedure● 10 Mbps● 100 Mbps● Autonegotiation● AutocrossingPROFINET with 100 Mbit/s full duplex (100BASE-TX)Yes; for Ethernet servicesYes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)YesYesProtocolsPROFINET IO DeviceServices— IRT— PROFIenergy— Prioritized startup— Shared device— Number of IO Controllers with shareddevice, max.Redundancy mode● PROFINET system redundancy (S2)Media redundancy— MRP— MRPDOpen IE communication● TCP/IP● SNMP● LLDPYesYesYesYesNoNoYes; with send cycles of between 250 µs and 4 ms in incrementsof 125 µsYesYesYes2Interrupts/diagnostics/status informationStatus indicatorAlarmsDiagnostics functionDiagnostics indication LED● RUN LED● ERROR LED● MAINT LED● Monitoring of the supply voltage (PWR-LED)● Connection display LINK TX/RXYes; green LEDYes; red LEDYes; Yellow LEDYes; green PWR LEDYes; 2x green link LEDs on BusAdapterYesYesYesPotential separationbetween backplane bus and electronicsbetween PROFINET and all other circuitsbetween supply and all other circuitsNoYes; 1 500 V ACNoPermissible potential differencebetween different circuitsSafety extra low voltage SELV6ES7155-6AA01-0BN0Page 3/4
05/21/2020
Subject to change without notice
© Copyright Siemens
IsolationIsolation tested with707 V DC (type test)Standards, approvals, certificatesNetwork loading classSecurity level2According to Security Level 1 Test Cases V1.1.1Ambient conditionsAmbient temperature during operation● horizontal installation, min.● horizontal installation, max.● vertical installation, min.● vertical installation, max.Altitude during operation relating to sea level● Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, seemanual0 °C60 °C0 °C50 °CConnection methodET-Connection● via BU/BA SendYes; + 16 ET 200AL modulesDimensionsWidthHeightDepth50 mm117 mm74 mmWeightsWeight, approx.last modified:190 g; IM 155-6 PN BA with 2x RJ45 ports and server module05/13/20206ES7155-6AA01-0BN0Page 4/4
05/21/2020
Subject to change without notice
© Copyright Siemens