Appendix D

FIRE APPARATUS ACCESS ROADS

SECTION D101GENERAL

D101.1Scope.Fireapparatusaccessroadsshallbeinaccor-dancewiththisappendixandallotherapplicablerequirementsof theInternational Fire Code.

D103.2Grade.Fireapparatusaccessroadsshallnotexceed10percent in grade.

Exception:Gradessteeperthan10percentasapprovedbythe fire chief.

D103.3Turningradius.Theminimumturningradiishallbedetermined by the code official.

D103.4Deadends.Dead-endfireapparatusaccessroadsinexcessof150feet(45720mm)shallbeprovidedwithwidthand turnaround provisions in accordance with Table D103.4.

TABLE D103.4

REQUIREMENTS FOR DEAD-END FIRE

APPARATUS ACCESS ROADS

LENGTH(feet)

WIDTH(feet)

TURNAROUNDS REQUIRED

SECTION D102REQUIRED ACCESS

D102.1Accessandloading.Facilities,buildingsorportionsofbuildingshereafterconstructedshallbeaccessibletofirede-partmentapparatusbywayofanapprovedfireapparatusaccessroadwithanasphalt,concreteorotherapproveddrivingsur-facecapableofsupportingtheimposedloadoffireapparatusweighing at least 75,000 pounds (34 050 kg).

0–150150–500

2020

None required

120 feet “Hammerhead,” 60 feet “Y” or96 feet diametercul-de-sacinaccordance with Figure D103.1120 feet Hammerhead, 60 feet “Y” or96 feet Diametercul-de-sacinaccordance with Figure D103.1Special approval required

SECTION D103

MINIMUM SPECIFICATIONS

D103.1Accessroadwidthwithahydrant.Whereafirehy-drantislocatedonafireapparatusaccessroad,theminimumroad width shall be 26 feet (7925 mm). See Figure D103.1.

501–750Over 750

26

For SI:1 foot = 304.8 mm.

60'95'

28'RTYP.'

26'

95'DIAMETERCUL-DE-SAC

70'

28'RTYP.'20'

70'DIAMETERCUL-DE-SAC

28'RTYP.'20'

ACCEPTABLEALTERNATIVET0120'HAMMERHEAD

20'

28'

20'

20'

MINIMUMCLEARANCE

AROUNDAFIRE

HYDRANT

30'30'60'60'

28'RTYP.'

28'RTYP.'

20'

20'

28'RTYP.'

20'

70'

28'

120'HAMMERHEAD

20'

20'

ACCEPTABLEALTERNATIVETO120'HAMMERHEAD

60'HAMMERHEAD

ForSI:1foot=304.8mm.

FIGURE D103.1

DEAD-END FIVE APPARATUS ACCESS ROAD TURNAROUND

2000 INTERNATIONAL FIRE CODE®361

APPENDIX DD103.5Fireapparatusaccessroadgates.Gatessecuringthefireapparatusaccessroadsshallcomplywithallofthefollow-ing criteria:

1.The minimum gate width shall be 20 feet (6096 mm).2.Gates shall be of the swinging or sliding type.

3.Constructionofgatesshallbeofmaterialsthatallowmanual operation by one person.

4.Gatecomponentsshallbemaintainedinanoperativeconditionatalltimesandreplacedorrepairedwhende-fective.

5.Electricgatesshallbeequippedwithameansofopeningthegatebyfiredepartmentpersonnelforemergencyac-cess.Emergencyopeningdevicesshallbeapprovedbythe code official.

6.Manualopeninggatesshallnotbelockedwithapadlockorchainandpadlockunlesstheyarecapableofbeingopened by means of forcible entry tools and

7.Lockingdevicespecificationsshallbesubmittedforap-proval by the code official.

D103.6Signs.Whererequiredbythecodeofficial,fireappara-tusaccessroadsshallbemarkedwithpermanentNOPARKING—FIRELANEsignscomplyingwithFigureD103.6.Signsshallhaveaminimumdimensionof12inches(305mm)wideby18inches(457mm)highandhaveredlettersonawhitereflectivebackground.SignsshallbepostedononeorbothsidesofthefireapparatusroadasrequiredbySectionD103.6.1 or D103.6.2.

SIGNTYPE\"A\"SIGNTYPE\"C\"SIGNTYPE\"D\"

PARKINGNOPARKINGNOPARKINGNOFIRELANEFIRELANEFIRELANE18\"12\"12\"12\"FIGURE D103.6FIRE LANE SIGNS

D103.6.1Roads20to26feetinwidth.Fireapparatusac-cessroads20to26feetwide(6096to7925mm)shallbeposted on both sides as a fire lane.

D103.6.2Roadsmorethan26feetinwidth.Fireappara-tusaccessroadsmorethan26feetwide(7925mm)to32feetwide(9754mm)shallbepostedononesideoftheroadas a fire lane.

SECTION D104

COMMERCIAL AND INDUSTRIAL DEVELOPMENTSD104.1Buildingsexceedingthreestories/30feetinheight.Buildingsorfacilitiesexceeding30feet(9144mm)orthree

362

FIRE APPARATUS ACCESS ROADS

storiesinheightshallhaveatleastthreemeansoffireapparatusaccess for each structure.

D104.2Buildingsexceeding62,000squarefeetinarea.Buildingsorfacilitieshavingagrossbuildingareaofmorethan62,000squarefeet(5760m2)shallbeprovidedwithtwosepa-rate and approved fire apparatus access roads.

Exception:Projectshavingagrossbuildingareaofupto124,000squarefeet(11520m2)havingasingleapprovedfireapparatusaccessroadwhenallbuildingsareequippedthroughout with approved automatic sprinkler systems.D104.3Remoteness.Wheretwoaccessroadsarerequired,theyshallbeplacedadistanceapartequaltonotlessthanonehalfofthelengthofthemaximumoveralldiagonaldimensionofthepropertyorareatobeserved,measuredinastraightlinebetween accesses.

SECTION D105

AERIAL FIRE APPARATUS ACCESS ROADSD105.1Whererequired.Buildingsorportionsofbuildingsorfacilitiesexceeding30feet(9144mm)inheightabovethelow-estleveloffiredepartmentvehicleaccessshallbeprovidedwithapprovedfireapparatusaccessroadscapableofaccom-modatingfiredepartmentaerialapparatus.Overheadutilityandpowerlinesshallnotbelocatedwithintheaerialfireappa-ratus access roadway.

D105.2Width.Fireapparatusaccessroadsshallhaveamini-mumunobstructedwidthof26feet(7925mm)intheimmedi-atevicinityofanybuildingorportionofbuildingmorethan30feet (9144 mm) in height.

D105.3Proximitytobuilding.Atleastoneoftherequiredac-cessroutesmeetingthisconditionshallbelocatedwithinaminimumof15feet(4572mm)andamaximumof30feet(9144mm)fromthebuilding,andshallbepositionedparallelto one entire side of the building.

SECTION D106

MULTIPLE-FAMILY RESIDENTIAL DEVELOPMENTSD106.1Projectshavingmorethan100dwellingunits.Mul-tiple-familyresidentialprojectshavingmorethan100dwellingunitsshallbeequippedthroughoutwithtwoseparateandap-proved fire apparatus access roads.

Exception:Projectshavingupto200dwellingunitsmayhaveasingleapprovedfireapparatusaccessroadwhenallbuildings,includingnonresidentialoccupancies,areequippedthroughoutwithapprovedautomaticsprinklersystemsinstalledinaccordancewithSection903.3.1.1or903.3.1.2 of theInternational Fire Code.

D106.2Projectshavingmorethan200dwellingunits.Mul-tiple-familyresidentialprojectshavingmorethan200dwellingunitsshallbeprovidedwithtwoseparateandapprovedfireap-paratusaccessroadsregardlessofwhethertheyareequippedwith an approved automatic sprinkler system.

2000 INTERNATIONAL FIRE CODE®

FIRE APPARATUS ACCESS ROADSSECTION D107

ONE- OR TWO-FAMILY RESIDENTIAL

DEVELOPMENTS

D107.1One-ortwo-familydwellingresidentialdevelop-ments.Developmentsofone-ortwo-familydwellingswherethenumberofdwellingunitsexceeds30shallbeprovidedwithseparateandapprovedfireapparatusaccessroads,andshallmeet the requirements of Section D104.3.Exceptions:

1.Wherethereare30orfewerdwellingunitsonasinglepublicorprivateaccesswayandalldwellingunitsareprotectedbyapprovedresidentialsprinklersystems,access from two directions shall not be required.2.Thenumberofdwellingunitsonasinglefireappara-tusaccessroadshallnotbeincreasedunlessfireappa-ratusaccessroadswillconnectwithfuturedevelopment, as determined by the code official.

2000 INTERNATIONAL FIRE CODE®APPENDIX D

363

32000 INTERNATIONAL FIRE CODE®