LW36-40.5(W)/T2500-31.5 型户外高压交流六氟化硫断路器
安装使用说明书 0SR.412.001.3
江苏省如高高压电器有限公司
2013年09月
目 录
1. 概述 ········································································1 2. 断路器结构及工作原理 ························································1 2.1 主要技术参数 ·······························································2 2.2 断路器的整体结构特点 ·······················································3 2.3 底架 ········································································3 2.4 极柱 ········································································4 2.5 断路器灭弧原理 ······························································7 3. 弹簧操动机构 ·································································7 3.1 弹簧操动机构 ·································································7 3.2 控制柜 ·······································································9 4. 电流互感器 ···································································10 5. 包装、运输及储存 ····························································10 5.1 包装 ········································································11 5.2 运输 ········································································11 5.3 存储 ········································································11 6. 安装、调整 ···································································11 6.1 地基的准备 ··································································11 6.2 断路器的安装 ································································12 6.3 接地 ········································································13 6.4 安装断路器的二次线 ··························································13 ····················································13 6.5 向断路器内充入SF6气体 ·
7. 安装后的现场测试 ·····························································14 7.1 试操作 ······································································14 7.2 安装后的检验与测试 ··························································14 7.3 清理现场 ···································································15 8. 使用与维护 ···································································15 9. 随机技术文件 ·································································16 10.订货须知 ····································································17 附录···············································································18
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
安装使用说明书
1 概述
1.1 本说明书适用于LW36-40.5(W)/T2500-31.5户外高压交流六氟化硫断路器,它详细描述了断路器的安装使用和维护的有关内容,以及在此过程中需要注意的安全规范和可能出现的危险。任何操作人员在安装和使用断路器前需仔细阅读本说明书,在确保熟悉相关内容后方可操作。如果仍有疑问或需要更详细的资料,请与制造商联系。
1.2 LW36-40.5(W)/T2500-31.5户外高压交流六氟化硫断路器适用于交流50Hz、35kV的电力系统中,是电力系统的控制和保护设备。该产品可进行频繁操作,并可作为联络断路器使用。同时适用于投切电容器组、电缆的工况。另外该产品可附电流互感器供测量与保护用。
1.3 断路器符合GB1984-2003《高压交流断路器》和IEC62271-100:2008《高压开关设备和控制设备——第100部分:交流断路器》及0SR.520.002《LW36-40.5(W)/T2500-31.5高压六氟化硫断路器技术规范》的要求。断路器以SF6气体为绝缘和灭弧介质,采用自能式灭弧原理,配用新型弹簧操动机构,具有开断能力强,操作功小,可靠性高的特点。 1.4 使用环境条件
a)周围环境温度 -30ºC ~+40ºC; b) 海拔高度 不超过3000m; c) 风速
不大于34m/s; 不大于25ºC; 不大于0.1w/cm;
2d) 日温差 e) 日照强度
f) 月平均相对湿度 不大于90%;
g) 地震加速度 水平不大于0.2g,垂直不大于0.1g; h) 覆冰厚度 不大于10mm;
i) 空气污秽程度 不超过GB/T 5582中的Ⅳ级; j) 安装场合
户外。
如果用户有特殊使用环境条件要求,请与制造商另行协商。
1.5 本说明书在叙述过程中分“注意”和“警告”两类提示,对于“注意”的有关内容,若不执行有可能造成不便或轻微伤害,对于“警告”的内容,若不执行有可能造成人身伤害或设备损坏,此两类提示均以黑体字示出。
2 断路器结构及工作原理
13DF577 葛轶群 编 制 校 核 标准化 审 定 倪晓霞 陈洁 崔国琴 吴鹏 20130927 20130927 20130927 20130930 C 重描 倪晓霞 20130930 页次 标记 处数 更改文件号 签 字 日 期 会 签 批 准 彭翔 20131008 第 1 页 共 23 页 LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
断路器采用三相瓷套支柱式结构,为户外设计,三相配用一个弹簧操动机构,居中布置。断路器以SF6气体作为绝缘和灭弧介质,运行时断路器三极SF6气体连通,并采用指针式密度继电器对其压力和密度进行监控。由于采用自能式灭弧原理,且在断路器运动系统中进行了优化设计,故有效的提高了机械效率,最大限度地降低了操作功。 2.1 主要技术参数
2.1.1断路器主要技术参数见表1。
表1 序号 1 2 项 目 额定电压 额定工频耐受电压(1min) 对地 断口间 对地 断口间 Hz A kA s kA A A μΩ MPa 次 mm kV 单位 参 数 40.5 95 95+23 185 185+30 50 2500 1.5 31.5 80 31.5 80 4 8 800 50 O-0.3s-CO-180s-CO ≤60(内附CT) 0.5 0.47/0.45 ≤0.5% ≤150 10000 ≥1256 ≥1256 8(内附CT) kg 1000(内附CT) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 额定雷电冲击耐受电压 额定频率 额定电流 首开极系数 额定短路开断电流ISC 额定短路关合电流(峰值) 额定短时耐受电流 额定峰值耐受电流 额定短路持续时间 额定失步开断电流 额定单个电容器组开断电流 额定电缆充电开断电流 额定操作顺序 主回路电阻 额定六氟化硫气体压力(20ºC表压) 报警/最低功能压力(20ºC表压) SF6气体年漏气率 SF6气体水分含量(μL /L) 机械寿命 爬电距离 每台充入SF6气体质量 每台断路器质量 断口间 对地 2.1.2机构主要技术参数见表2。
表2 序号 名 称 额定电压Ue 1 储能电动机 额定输出功率 正常工作电压范围 储能时间(额定电压) 手动储能力矩 分闸电磁铁额定电压/电流 合闸电磁铁额定电压/电流 单位 V W V s N·m V/A V/A 参 数 值 DC220/AC220/DC110 500 85%Ue~110%Ue ≤20 ≤60 DC220/2.0,DC110/3.8 DC220/1.4,DC110/2.2 2 3 4 5 第 2 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 表2(续) 序号 6 7 8 9 10 名 称 额定工作电压 辅助开关 额定工作电流 接点数:常开/常闭 接线端子能通过的持续电流 机构输出轴工作转角 加热器及照明回路电压 辅助回路工频耐受电压 单位 V A 对 A 度 V kV 参 数 值 DC220/DC110 3/5 11/11 10 50 AC220 2kV,1min或2.5kV,1s 2.1.3产品的机械调整参数见表3。
表3 序 号 1 2 3 4 5 6 7 8 名 称 最小空气绝缘距离 三极分闸同期性 三极合闸同期性 合闸时间(额定电压下) 分闸时间(额定电压下) 合-分时间(金属短接时间) 分-合时间(自动重合时) 开断时间 单 位 mm ms ms ms ms ms ms ms 参 数 值 440 ≤2 ≤3 ≤100 ≤60 ≤80(运行时≥80) 300 ≤65 2.2 断路器的整体结构特点
该型断路器的整体结构如图1所示,三个极柱安装在共同的底架上。控制柜居中吊装在底架下面,柜内装有弹簧操动机构和控制单元,机构的输出杆与中相的拐臂相连。并通过连杆与A、C相断路器的拐臂箱连接进行分、合闸操作。三相SF6气体连通,并采用SF6气体密度继电器对断路器内的SF6气体密度进行监控。 2.3 底架
底架(图1所示序2)起支撑三瓷柱并连接控制柜的作用,是由钢板整体弯制而成。底架内有三相SF6气体充气管路和指针式密度继电器,背面有密度继电器观察孔可观察到SF6气体的压力值。另外底架内还装有多通体及LF-5截止阀,通过多通体可对本体内充气及放气,同时截止阀可将密度继电器内气体与本体内的气体隔离,便于密度继电器的校验及检修。
具有温度补偿指针式SF6密度继电器用于对设备内SF6气体的密度进行监视并发出控制信号,
功能。当环境温度变化而引起SF6气体的压力变化时,密度继电器不会动作。只有当SF6气体泄漏引起气体压力变化时,控制器才会发出报警及闭锁信号。 注意:密度继电器所示值为20℃的压力值。
第 3 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 单位为毫米
1.极柱 2.底架 3.密度继电器 4.弹簧操动机构及控制柜 5.铭牌
图1 断路器整体结构图(内附CT)
2.4 极柱
每一极柱为一气密单元。极柱自上而下,分为上出线板、灭弧室、下出线板、支柱瓷套、绝缘拉杆、拐臂箱等几部分组成(如图2),下面分述如下: 2.4.1 上、下出线板
上、下出线板为线路一次接线用,上下出线板在极柱正反两面皆有出线,出线板其出线方向 第 4 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 可根据用户需要进行安装。上、下出线板的接线孔尺寸按照2500A接线方式,见图3,其尺寸规范参照GB/T 5273《变压器、高压电器和套管的接线端子》。
1.帽 2.上接线板 3.灭弧室 4.内置电流互感器 5.筒 6.下接线板 7.支柱瓷套 8.绝缘拉杆
9.互感器二次线引线管 10.拐臂箱 11.互感器接线板 12.输出轴
图2 极柱
单位为毫米
图3 接线板
第 5 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 2.4.2 灭弧室
灭弧室整体安装在灭弧室瓷套内,是断路器的核心部件。它主要由瓷套、静触头支座、静主触头、静弧触头、喷口、气缸、动弧触头、表带触指、下支撑座、拉杆等零部件组成(见图4)。另有吸附剂装在灭弧室顶部,拉杆8与支柱瓷套内的绝缘拉杆相连,并最终连至拐臂箱内的传动轴。
长期载流回路是由上接线板、静触头座、主触指、活塞、表带触指、气缸、下支撑座、导电杆和下接线板组成。在开断电流的过程中,由装在静触头座上的静弧触头和装在动主触头的动弧触头起引导电弧的作用。活塞的热膨胀室下部装有单向阀,压气室下部装有回气阀和释压装置。
1.静弧触头 2.静主触头 3.喷口 4.动弧触头 5.活塞 6.气缸 7.下支撑座 8.拉杆
图4 灭弧室结构图
2.4.3 支柱瓷套
支柱瓷套起支撑灭弧室和对地绝缘的作用。瓷套内装有绝缘拉杆,起对地绝缘和机械传动作用。支柱瓷套也由优质高强度瓷制成,具有很高的强度和很好的气密性。 2.4.4 拐臂箱
拐臂箱的作用是将操动机构的输出动作传递到绝缘拉杆,并最终传递到灭弧室运动部件单元,完成断路器的分、合闸动作。拐臂箱上装有自封阀,用于连接底架内的充气管道。拐臂箱壳 第 6 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 体由高强度气密性的铝合金铸造而成,在其上面设有定位孔,可以方便的将极柱固定在分闸位置。 2.5 断路器灭弧原理(见图5)
该灭弧室在大电流阶段采用自能式灭弧原理,当断路器接到分闸命令后,以活塞、动弧触头、拉杆等组成的刚性运动部件在分闸弹簧的作用下向下运动。在运动过程中,静主触指先与动主触头(即活塞)分离,电流转移至仍闭合的两个弧触头上,随后弧触头分离形成电弧。
在开断短路电流时,由于开断电流较大,故弧触头间的电弧能量大,弧区热气流流入热膨胀室,在热膨胀室进行热交换,形成低温高压气体;此时,由于热膨胀室压力大于压气室压力,故单向阀6关闭。当电流过零时,热膨胀室的高压气体吹向断口间使电弧熄灭。同时在分闸过程中,压气室的压力开始被压缩,但到达一定的气压值时,底部的弹性释压阀7打开,一边压气,一边放气,使机构不需要克服更多的压气反力,从而大大降低了操作功(见图5B)。
在开断小电流时(通常在几千安),由于电弧能量小,热膨胀室内产生压力小。此时压气室内的压力高于膨胀室内压力,单向阀6打开,被压缩的气体向断口吹去。在电流过零时,这些具有一定压力的气体吹向断口使电弧熄灭(见图5C )
A B C D
合闸位置 开断大电流 开断小电流 分闸位置
1.静弧触头 2.静主触头 3.喷口 4.动弧触头 5.活塞 6.单向阀 7.释压阀 8.减压弹簧9.压气室10.热膨胀室
图5 灭弧原理
3 弹簧操动机构
3.1弹簧操动机构(见图6)
第 7 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
1.输出连杆 2.合闸扇形板 3.合闸半轴 4.输出轴 5.输出拐臂 6.合闸拐臂 7.分闸扇形板 8.分闸半轴 9.分闸缓冲器 10.分闸拉杆 11.分闸大弹簧 12.分闸小弹簧 13.合闸拉杆 14.合闸大弹簧 15.合闸小弹簧 16.传动齿轮 17.传动轴 18.凸轮 19.储能轴
图6 弹簧操动机构
3.1.1合闸弹簧的储能
电机接到储能命令后通电转动,通过三级齿轮传动,使储能轴19转动,合闸弹簧14和15储能,储能到位(即弹簧过中)后,固定于机构箱上的轴销使驱动棘爪与储能轴19上的套脱离啮合(此时储能轴顶开行程开关,从电气上使电机停转),靠电机的惯性运动,带动凸轮18上的滚轮及合闸扇形板2扣接在合闸半轴3上,使机构处于分闸已储能位置。 3.1.2 合闸操作
合闸脱扣线圈在接到合闸命令后动作,使合闸半轴3顺时针方向转动,从而使储能保持解除, 第 8 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 在合闸弹簧的作用下,使储能轴顺时针转动。储能轴上凸轮随着储能轴的转动驱动输出拐臂5上滚子使内输出拐臂转动,并带动输出轴4一起转动,再由固定在输出轴上的机构外输出拐臂通过分闸弹簧拉杆10和机构输出杆1、断路器本体上的外拐臂把运动传给灭弧室,从而使灭弧室中的触头闭合,完成三相合闸动作。
在内输出拐臂转动的过程中,输出拐臂上另一滚子驱动分闸扇形板7沿其轨迹转动,在合闸过冲的瞬间,分闸扇形板在其上复位弹簧的作用下被扣接在分闸半轴8上,使断路器保持在合闸状态。
与此同时,分闸弹簧11和12在机构外输出拐臂和分闸弹簧拉杆10的作用下进行储能,合闸完成后,分闸簧也储能结束,产品具备分闸条件。
当合闸操作发生的时候,储能电机就接通了,随即在15s内重新储能。此时,机构处于合闸已储能位置。
为防止操动机构再次合闸,产品有机械联锁和电气防跳。合闸弹簧和分闸弹簧储能完成后,断路器就作好了进行一次O-C-O操作顺序的准备。 3.1.3 分闸操作
分闸脱扣线圈在接到分闸命令后,使分闸保持解除,分闸弹簧释放能量,通过分闸弹簧拉杆,带动机构的内、外输出拐臂运动至分闸位置,同时灭弧室中的触头由机构输出连杆带着运动到分闸位置。
最后分闸运动的动能通过内输出拐臂由分闸缓冲器9吸收。分闸缓冲器也起最后止住分闸运动的功能。同时,分合指示牌指向分闸位置,并使辅助开关切换。 3.1.4 重合闸操作
由于断路器在合闸位置时,合闸弹簧已储能,故断路器可以执行O-0.3s-CO的重合闸操作。 3.2 控制柜
控制柜内装有弹簧操动机构,此时机构电气控制分为分合闸控制、电机储能控制、加热器控制及SF6气体异常控制共四个部分。
控制柜的内面板上有手动分合闸按钮,远方-就地转换开关,机构输出轴前端有断路器状态的指示牌。操作人员可随时直观地看到断路器所处的状态。
第 9 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
图7 弹簧操动机构原理示意图
4 电流互感器
4.1 每台断路器可内附6~12只套管式电流互感器(以下简称互感器)。每相装2~4只,导电杆为一次线,互感器本身只有环形铁芯及绕组。互感器排列及二次出线编号见附录B。二次绕组出线通过密封良好的接线板引至外部,接线板引线通过底箱引到机构箱内,并用玻璃纤维软管保护。 4.2 互感器有两种型号:LRG-35LW型供测量用,LRGB-35LW型供差动保护用。每种规格可以有两个抽头,可以获得三种电流比,利用机构箱内的接线端子可以方便地改变电流比。
4.3 特殊规格的互感器可由用户与制造商协商,制造商可为用户定制。如二次电流为1A、提高精度等。
4.4 互感器二次接线:每相互感器的二次引线均通过各自的密封良好的接线板引出,经底箱引至机构箱内,导线截面积为2.5mm。如果某一个二次绕组不用,则应将首末端子短接接地。
2
5 包装、运输及储存
第 10 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 5.1 包装
本产品主要使用于户外,采用解体简易的木箱封闭式包装,其中包括,备品配件的包装。 注意:1、产品预充有0.03MPa-0.05MPa的SF6气体。
2、分闸弹簧与合闸弹簧均处于释放状态。
5.2 运输
各包装组件可用铲车搬移或吊车(起重大于1吨)吊运,搬移过程中要平移轻放。长途运输可以用汽车、火车、轮船发运。包装后的断路器在运输装卸时不得翻转、倒置,不得受强烈震动和碰撞。
警告:1、瓷件为脆性材料,不按规范运输会造成极柱瓷体的损坏。 2、严禁在产品充气压力大于0.05MPa下运输或搬移。 5.3 存储
如果断路器发运到现场后没有立即安装,各包装组件最好在户内存储。若条件不许可,也可以在户外放置,但各组件应置于通风处,为避免地面潮湿,木箱应置于厚木板上并用防雨帆布覆盖。长期存放时,控制柜的防凝露加热器应投入。户外最长储存期不宜超过半年。
附件箱最好放户内保存,因为所装的专用附件为非户外设计零件。
6 安装、调整
安装前请先按装箱单验收各组件及附件,若有疑问请立即同制造商联系。 警告:1、严禁自行将断路器与机构解体。
2、若包装组件吊装不当,会造成倾倒,引起设备损坏和人身事故。
3、安装过程中使用不合适的螺栓或紧固方式不当,会造成产品倾倒,引起设备损坏和人身事故。安装紧固件用力矩扳手紧固。紧固力矩如下: M6 8±1N·m M8 22±2N·m M10 45±5N·m M12 70±7N·m M16 200±20N·m
注意:1、整体安装过程中需要有熟练技术和安装经验的专业人士现场指导。
2、请勿使用任何工具或起重设备碰击瓷套。
6.1 地基的准备
断路器地基要求如图8所示。两个基面的高度差不超过2mm,每个基面的水平度不超过2mm。8只地脚螺栓可根据要求由制造商提供。
第 11 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
单位为毫米
图8 安装基座图
6.2 断路器的安装
安装组件前,先拆除外覆塑料包扎,如图9所示,用起重设备将组件稍吊起,拆除底部的垫木,然后将其吊运至地基处,用8个M20的螺母将其固定在地基上。
目测检查每个极柱的瓷体是否在运输过程中发生破损或裂缝,若有此类情况请及时与制造商联系。
警告:若瓷件在破损或有裂缝的状态下充气操作,有可能会发生瓷体爆炸,危及人身安全。 注意:产品出厂时机构输出杆长度及相间连杆长度已调整好,请勿随意调整。
第 12 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
图9 断路器基座在地基上的安装
6.3 接地
在支架的支脚上有接地螺栓孔,用户可根据实际需要接地。接地前,用砂布打磨接地处接触面,再在接触面上涂一层薄薄的无水凡士林。 6.4 安装断路器的二次线
控制柜框架底板上有供用户连接二次电缆线的盖板,用户可参考接线图连接二次线。 注意:1、二次线必须在不带电状态下连接。
2、二次线必须在操动机构的分合闸弹簧都释放的状态下连接。 6.5 向断路器内充入SF6气体
首先拆下底架内充气接头的保护螺母,连接充气装置。气瓶内的SF6气体通过减压阀、充气管和底架内密度继电器下部的三通接头向三极柱充气,见图10。充气前,应先用0.1MPa的SF6气体冲洗减压阀和充气管5s~10s,以排除充气管路内的空气,待管路内的水蒸气被排出后,保持0.1 MPa的压力拧上管路接头,随后慢慢加压。在充气过程中,减压阀应控制在0.5 MPa以下,注意观察减压阀表数值和压力表数值,直至充气压力稳定达到0.50MPa。充气完成后,将充气装置拧下,封上自封阀堵头,并妥善保存。
第 13 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
1.SF6 气瓶 2.减压阀 3.安全阀 4.精密压力表 5.充气管 6.充气接头 7.三通接头 8.指
针式密度继电器 图10 SF6充气装置的连接
注意:1、指针式密度继电器压力表显示的数值为20℃时的表压;
2、充气过程中,充气管凝霜为正常现象,可调整减压阀门适当降低流速;
3、充气压力最多可至0.52MPa(20℃);
4、本体中的气体压力值以密度继电器为准,不可参考氧气表值。
7 安装后的现场测试
7.1 试操作
安装工作完成后,断路器处于分闸位置,合闸弹簧未储能。完成断路器五次合闸、五次分闸、三次标准循环操作。
警告:1、操作前检查断路器在运动方向上是否有阻挡物未拆除。
2、一次端子不能与高压系统相连。
3、无论在任何情况下操作,SF6气体压力不得低于0.3MPa,否则会引起断路器机械损伤。4、检查所有销连接是否被紧定。
5、试操作最好采用电动远方控制,操作前所有操作人员应站在15m外有屏障的地方。 6、在任何情况下,严禁断路器单相或两相操作。 7.2 安装后的检查与测试
7.2.1 机械操作特性测量
7.2.1.1 在分闸与合闸操作过程中,记录弹簧操动机构储能时间、分闸时间、合闸时间及分合闸同期性。
7.2.1.2 断路器速度的测量:断路器的速度,现场一般无需测量。只有当断路器的其他特性有问 第 14 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 题或检修后需重新测量时,可以跟制造商联系。或用户按有关规定自己测量。
建议用专用的速度特性仪器进行测量。
注意:测速度是在额定操作气压和额定工作电压下进行的。 7.2.2 主回路电阻测量
在合闸状态下,用主回路电阻测量仪测量三相的主回路电阻,并记录。 7.2.3 工频耐压试验
若条件许可,对断路器进行工频耐压试验,并作记录。 7.2.4 检查指针式密度继电器的性能
将截止阀关闭,用专用的放气接头接在底架内的充气接头上,轻拧螺母,使密度继电器内气体缓缓泄漏。待SF6气体压力降至报警压力时,应能报警;待压力降至闭锁压力时,检查断路器是否处于闭锁状态。
注意:检查后,将放气接头拧下,装回保护螺母,并妥善保存,同时打开LF-5截止阀。 7.2.5 断路器的检漏
用检漏仪检查断路器所有密封面的气密性,尤其是检查充气管路、接头是否漏气。若接头有漏气现象,可拆下接头,观察密封面是否有异物或O型密封圈是否有损伤,处理更换后重新检漏。若发现极柱密封面有泄漏现象,须及时通知制造商前来解决。 7.2.6 微量水份测量
在充气阀上接减压阀、管路和微量水份测试仪,测量断路器气室内的水份含量。验收时不应(充气后24h测量),运行时不大于300×10(V/V,20ºC)。 超过150×10(V/V,20ºC)7.2.7 检查温湿度控制器与加热器
检查温湿度控制器与加热器投切是否正常。 7.2.8 打磨接触面
连接一次母线与断路器一次接线端子,连接方向由用户根据现场情况决定。接线时将接触面砂磨至发亮,并用白布沾酒精擦洗干净,涂上一层薄薄的无水凡士林。 7.2.9 用清水擦洗断路器所有瓷件
用清水擦洗断路器所有瓷件。 7.2.10 保存数据
投运前再次检查测试项目,核对实验数据,填写安装检测试验报告,一式两份,用户与制造商各持一份,作为原始资料备查。
7.3 清理现场
第 15 页 共 23 页
-6
-6
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
至此断路器安装完毕,盖上所有的盖板,将拆下的零件保管好,以备后用。
8 使用与维护
为了保证产品良好的工作,正常的维修是必要的,表4、表5和表6中列出了推荐的维修计划、检修周期和项目。由于断路器中SF6气体处于密封之中,损耗可以忽略不计,所以一般来讲主要考虑操作机构及传动部分的检查维修。
表4推荐的维修计划 检 查 巡检 年检 大修 周 期 每周 每2年 每10-15年 说 明 检查断路器是否有任何不正常 较短时间停止运行进行检修 较长时间停止运行对每部分进行检修 表5推荐的主触头检修周期 条 件 次 数 额定电流开断 5000 额定短路电流开断 21 注:1.用于投切电容器组工位的断路器,当关合次数达到1000次(涌流≥3kA)或2000次(涌流<3kA)时,灭弧室应返厂检修; 2.若断路器操作次数达到6000次以上时,产品应进行大修。 表6维修时的检查项目 维修分类 P R M ○ ○ 检查瓷瓶的损坏与污秽 ○ ○ 检查主接线端的颜色变化 ○ ○ 检查接地端的松动情况 1 外观 ○ ○ 检查位置指示器 ○ ○ ○ 记录断路器的操作次数 ○ ○断路器行程及接触行程 ○ 触头、喷口检修、更换新的 ○ 更换吸附剂 2 本体 ○ ○主回路电阻测量 ○ 更换密封圈 ○○机构尺寸测量 ○ ○ ○机构润滑 3 操作机构 ○ 紧固螺栓及更换轴用挡圈 ○ ○ 检查缓冲器是否漏油 ○测量SF6的压力和环境温度 ○○4 SF6气体系统 SF6气体水分检测 ○对拆卸部位进行检漏 ○ ○ ○ ○ 检查SF6压力开关的整定 ○检查辅助开关的触头 ○○ 检查控制线路的松动 5 控制系统 ○ ○测量控制回路的绝缘电阻 ○ 检查加热器是否正常 6 操作 测定分合闸时间及速度等 ○ ○ 注:表中P、R、M分别表示:巡视检查、年检及大修,SF6水分测定应定期进行(建议一年一次),产品运行中的水分含量不大于300PPm(V/V)。 序号 项 目 检 查 内 容 9 随机技术文件
第 16 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3 9.1 安装使用说明书 一份 9.2 装箱单 一份 9.3 产品合格证明书 一份
10 订货须知
10.1 订货时必须明确产品的型号、使用环境条件、基本技术参数(如额定电压、额定电流、额定短路开断电流、控制电压、电机电源电压等)、二次控制部分是否带防跳回路(若不注明,正常按不带防跳回路方案)、内附的参数等。
10.2 如果对产品的部分技术参数有更多或更高的要求,请与制造商协商。 10.3 需要备品、配件、专用工具、专用设备名称和数量(见附录A)
第 17 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
附录A (规范性附录) 安装工具及备品一览表 表A.1随机附件及辅助材料 名称 六氟化硫气体 充气管 密封垫圈 手动储能手柄 密度继电器接口密封圈 自封阀处密封圈 名称 分、合闸线圈 电机 行程开关 交流接触器(直流接触器) 测速工具 名称 六氟化硫气体检漏仪 微量水份测量仪 主回路电阻测量仪 机械特性测试仪 氧气减压阀 真空泵 型号 5RG.177.361.6 5RG.465.361.2 5RG.371.372.1 8RG.370.361.14 型号 型号 数量 1瓶(8Kg) 1套 5只 1个 1 只 2 只 数量 1套 1件 1件 1件 1件 数量 1台 1台 1台 1台 1台 1 台 备注 借LW36-126 备注 需另行订货 需另行订货 需另行订货 需另行订货 需另行订货 备注 需另行订货 需另行订货 需另行订货 需另行订货 需另行订货 需另行订货 表A.2按订货合同可提供的备件及专用工具 表A.3按订货合同可提供的专用设备
第 18 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
附录B
(规范性附录)
内附电流互感器端子排列图及位置图 148 A4S4 147 A4S3 146 A4S2 145 A4S1 144 A3S4 143 A3S3 142 A3S2 141 A3S1 140 A2S4 139 A2S3 138 A2S2 137 A2S1 136 A1S4 135 A1S3 134 A1S2 133 A1S1 132 B4S4 131 B4S3 130 B4S2 129 B4S1 128 B3S4 127 B3S3 126 B3S2 125 B3S1 相端子号为133-148。
124 123 122 121 120 119 118 117 116 115 114 113 112 111 110 109 108 107 106 105 104 103 102 101 B2S4 B2S3 B2S2 B2S1 B1S4 B1S3 B1S2 B1S1 C4S4 C4S3 C4S2 C4S1 C3S4 C3S3 C3S2 C3S1 C2S4 C2S3 C2S2 C2S1 C1S4 C1S3 C1S2 C1S1 说明:1.面对机构箱正面,左侧边相为C相。C相端子号为101-116,B相端子号为117-132,A 2.当每相电流互感器为三只二次绕组或两只二次绕组时,端子由DP-101往后依次排列,
无二次绕组二次引线空号,所空的端子可不安装,其余仍按上图排列。
3.如每相有五只或五只以上绕组时,端子号另按特供接线图排列接线。
图B.1 内附电流互感器端子排列图
第 19 页 共 23 页
LW36-40.5(W)/T2500-31.5型户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
说明: 1、断路器的上接线端子为L1,互感器如图示位置,按减极性标注,一次侧L1为正,二次
侧S1出正。
2、一般情况下,每相电流互感器二次绕组测量级由上往下组合排列。
图B.2 内附电流互感器位置图
第 20 页 共 23 页
LW36-40.5(W)/T2500-31.5户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
附录C (规范性附录)
电气原理图及电器元件其端子接线图
图C.1 LW36-40.5断路器电气原理图1(0SR.352.085)
第 21 页 共 23 页
LW36-40.5(W)/T2500-31.5户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
图C.2 LW36-40.5断路器电气原理图2(0SR.352.085)
第 22 页 共 23 页
LW36-40.5(W)/T2500-31.5户外高压交流六氟化硫断路器安装使用说明书 0SR.412.001.3
图C.3 LW36-40.5断路器电气原理图3(0SR.352.085)
第 23 页 共 23 页